Monday – Friday, 09:00 – 18:00 (UTC+3) WhatsApp 24/7

Cable Short-Circuit Thermal Withstand Calculator

The I²t ≤ k²S² check: k is computed from the formula in Annex A of IEC 60364-5-54 rather than read from a table, and the tool returns the minimum size required and the longest time the size can carry the fault.

Calculator

Derives k from the conductor, insulation and size, then compares it against the I²t the circuit lets through and says whether the cable withstands it.

The constants follow this choice: copper ρ₂₀ = 17.241×10⁻⁶ Ω·mm, aluminium 28.264×10⁻⁶

The nominal size from the catalogue — not a measured copper area

The conductor temperature at the instant the fault starts. For a line conductor the maximum continuous operating temperature is taken as the worst case in design; a protective conductor outside the cable that carries no load starts cold, and a core of the cable sits at the same temperature as the loaded cores. For a phase conductor or a cable core, read it from the cable’s data sheet (manufacturer). 75 is only an EXAMPLE — while the field holds it the results carry “(example value)”

The limit temperature the insulation can survive briefly in a short circuit; the cable standard gives it per insulation type; read it from the cable’s data sheet (manufacturer). 180 is only an EXAMPLE — while the field holds it the results carry “(example value)”

If the clearing time is below 0.1 s, or the device is current-limiting, the second route is mandatory

The prospective symmetrical rms value. Check it at both ends of the run — each end gives a different worst case

Read from the protective device’s time-current curve at Ik

The declared Joule integral. For fuses use the total value — the pre-arcing value is for discrimination studies. There is no single catalogue number: let-through I²t varies with applied voltage, available fault current and power factor, so read the value at your own Ik and voltage

Result

—Calculated k
—Permitted k²S²
—I²t let through by the circuit
—Result
—Safety margin
—Minimum size required
—Longest time this size can carry it
—Warning

The calculation runs entirely in your browser; nothing you type is sent to our servers. Only if you press “Request a quote with this calculation” are your inputs and the result written to your browser’s session storage, so it can be carried into the quote form.

Worked example

Opened with its default case — Conductor material: Copper · Cross-sectional area (mm²): 16 · Initial temperature θi (°C) — read it from your cable standard or specification: 75 — the calculator returns the figures below. They are written out here so the output is readable without running JavaScript: in print, with scripts disabled, or by a search engine.

Worked example — inputs
InputValue
Conductor materialCopper
Cross-sectional area (mm²)16
Initial temperature θi (°C) — read it from your cable standard or specification75
Final temperature θf (°C) — read it from your cable standard or specification180
How will the energy be given?Current (kA) and clearing time (s)
Short-circuit current Ik (kA)6
Clearing time t (s)0.2
Worked example — results
ResultValue
Calculated k122 (calculated 121.97; θi 75 °C → θf 180 °C) (example value)
Permitted k²S²3,810,304 A²s (k²S² at 16 mm²) (example value)
I²t let through by the circuit7,200,000 A²s (6 kA for 0.2 s)
ResultFAILS — 7,200,000 > 3,810,304 A²s (example value)
Safety margin47.08% short — the required size is 1.37× the one entered (example value)
Minimum size required25 mm² (calculated 22 mm²) (example value)
Longest time this size can carry it0.11 s — the longest this size can carry it (example value)
Warningθi and/or θf is still at the pre-filled EXAMPLE value: read it from your own cable standard or specification — this result is not a standard’s figure. k was rounded UP to the nearest integer (raw 121.97). Published tables may round some cells down — confirm k against your own cable standard for a critical design. This checks only the CONDUCTOR’s thermal withstand. Screen/armour, harmonic-loaded neutrals, parallel runs and electrodynamic forces are out of scope. For a protective conductor, θi depends on its position: one outside the cable that carries no load starts cold; a core of the cable starts at the same temperature as the loaded cores — choose θi accordingly. θf also varies with the insulation type and, in some standards, with the conductor cross-section; read the value for your size from your own standard.

Change any field above and the calculator recomputes; this table is the default case only. Thresholds and class values that come from a standard are not built into the tool: you type the values you read from your own standard or specification into the relevant fields. The pre-filled thresholds in this table are only an example — read yours from your own standard.

Short answer

Will the cable withstand a short circuit?

It is tested by a single inequality: the energy released in the fault must be smaller than the energy the conductor can absorb.

I² · t ≤ k² · S² — where I is the short-circuit current, t the clearing time of the protective device, S the nominal cross-sectional area, and k a factor derived from the conductor material and the temperature the insulation can survive. The relation is given for short-circuits lasting up to 5 seconds.

This tool does not read k from a table — it computes it. Why, and how, is set out below.

This is a separate check from voltage drop

Sizing a cable does not rest on one calculation. A voltage-drop calculation finds what the run loses in steady state; this page tests whether the conductor melts during a fault. Neither substitutes for the other and they usually suggest different sizes — the binding one is the larger.

On long runs voltage drop usually decides; on short runs close to the main board, with high prospective fault current, short-circuit withstand usually decides.

Where does k come from?

k is derived on the assumption that the conductor absorbs the heat of the fault while losing none of it — the adiabatic assumption. The method is in normative Annex A of IEC 60364-5-54:

k = √( Qc · (β + 20) / ρ₂₀ · ln( (β + θf) / (β + θi) ) )
Qc volumetric heat capacity of the conductor material · β the reciprocal of the temperature coefficient of resistivity at 0 °C · ρ₂₀ resistivity at 20 °C · θi initial and θf final temperature

Material constants in the formula
QuantityCopperAluminium
Qc — volumetric heat capacity (J/(K·mm³))3.45 × 10⁻³2.50 × 10⁻³
β — reciprocal of the temperature coefficient of resistivity at 0 °C (°C)234.5228
ρ₂₀ — resistivity at 20 °C (Ω·mm)17.241 × 10⁻⁶28.264 × 10⁻⁶

The unit of ρ₂₀ is Ω·mm, not Ω·m: copper’s 1.7241 × 10⁻⁸ Ω·m is 17.241 × 10⁻⁶ Ω·mm. Confusing the two throws k out by a factor of 31.6 — it is the most likely mistake if you build the formula yourself.

Why a formula rather than a table? Two reasons. The first is legal: the k values published in the standard are part of a copyrighted compilation, whereas the formula and the physical constants are facts — we run the method, we do not copy the values. The second is practical: a table gives you a handful of ready combinations, the formula works for any θi/θf pair you enter.

Rounding is to the nearest integer. The formula produces a continuous number; published tables give integers. We tested all eleven published cells: rounding to nearest matches ten of them, rounding down only four. The interesting part is that two cells with almost the same raw value are rounded in opposite directions in the table — so the table itself does not round consistently. The tool therefore follows the formula, and tells you when it has rounded k upwards.

Where do the temperatures come from?

θi is the conductor temperature at the instant the fault starts; in design it is taken as the worst case, the maximum continuous operating temperature. θf is the limit the insulation can survive briefly, and it comes from the cable standard.

The two temperatures the tool asks for
QuantityWhat it meansWhere to read it
θi — initial temperatureThe conductor temperature at the instant the fault starts. For a line conductor the maximum continuous operating temperature is the design worst caseThe cable standard or the cable’s data sheet
θf — final temperatureThe limit the insulation can survive briefly; it depends on the insulation typeThe cable standard (short-circuit temperature limits for cables)
θi for a protective conductorAn insulated protective conductor outside the cable that carries no load starts at ambient; a core of the cable, or a bunched conductor, sits at the same temperature as the loaded coresThe standard’s protective-conductor clause and the cable’s build

An easy mistake lives in the last row. Using a cold (ambient) starting temperature for the PE core of a multicore cable overstates k — you believe the conductor is tougher than it is. Choose θi according to how the cable is built.

The tool holds no ready-made temperature for any insulation: for every case, mineral-insulated cable and bare protective conductors included, you read θi and θf from your own cable standard or specification and enter them. The values pre-filled in the fields (75 and 180) are only an example — do not read them as standard values, and while a field holds its pre-filled value the results carry “(example value)”. For some insulations θf also varies with cross-section; if your standard makes a distinction by size, enter the value that matches your size.

Time, or let-through I²t?

The tool has two input modes because a single “time” box would give the wrong answer in two of the three situations below.

Which input, when
SituationWhat to useWhy
Clearing time roughly above 0.1 s, device not current-limitingt read from the time-current curveThe curve gives a meaningful time in this region
Clearing time below 0.1 sThe manufacturer’s let-through I²tIn the first half-cycles the current is asymmetrical (DC component); the symmetrical rms value understates the real energy
The device is current-limitingThe manufacturer’s let-through I²tThe device cuts the current before it reaches its peak; there is no time left to read from a curve
Protection is by fuseThe total I²tThe pre-arcing value is for discrimination studies; cable protection uses the total value

A common misreading: “below 0.1 s the adiabatic assumption breaks down.” The opposite is true — the shorter the fault, the less heat escapes into the insulation and the better the assumption holds. The threshold is not about heat; it is that the current itself can no longer be read off a curve.

What does the 5-second limit mean?

The adiabatic relation assumes all the heat stays in the conductor. The longer the fault lasts, the further that drifts from reality: part of the heat escapes into the insulation and the surroundings. That is why the standard gives the relation for short-circuits lasting up to 5 seconds.

Longer durations need a non-adiabatic calculation — IEC 60949 is the standard for that — and the result comes out more optimistic than the adiabatic one. Even so, a result beyond 5 seconds is treated as invalid, because the relation you used was not given for that range — recalculate with IEC 60949.

What this check does NOT cover

In one sentence: only the thermal withstand of the conductor. Each of the following is a separate calculation, and in practice one of them is sometimes the binding one.

  • Screen and armour. A screened cable has two different fault levels: symmetrical three-phase for the conductor, line-to-earth for the screen. Because the screen is usually far thinner than the line conductor, the screen is frequently the limiting element, not the conductor.
  • Neutral conductors and harmonics. With loads that generate triplen harmonics (LED drivers, switch-mode supplies, UPS) the neutral current can exceed the line current, and a cable with a reduced neutral is then thermally inadequate. A check made on the line conductor does not see this at all.
  • Parallel cables. During a fault the current does not simply divide between the legs: a faulted conductor is fed from both ends, and once the protection in one leg opens the remaining legs take over. Equal lengths and a common route are a separate condition again.
  • Motor circuits. The cumulative heating of successive starts is not a short-circuit event but a cyclic overload; this relation models a single event. In motor circuits the cable is usually protected against short-circuit only, with overload protection sitting in the motor starter.
  • Transformer secondaries. The cable between the transformer and the main board is often unprotected at its origin, with very high fault current and a dominant DC component — exactly the region where let-through I²t must be used.
  • Disconnection at the minimum fault current. I²t ≤ k²S² is a necessary condition, not a sufficient one: you must separately prove that the protective device also operates in the required time at the smallest fault current, at the far end of the run. The largest current at the origin drives this calculation; the smallest current at the far end drives the disconnection check.
  • Electrodynamic forces. Short-circuit current pushes and pulls conductors. Busbars, cable supports, cleat spacing and terminations need a separate mechanical calculation; this page counts heat only.

Scope (AKSCO): we supply materials in this field — cable, panel equipment, switchgear and consumables. We do not provide electrical design, calculation approval or commissioning services. This tool is a preliminary design aid; the final verification is made by a qualified electrical engineer against the edition of the standard in force.

The number is too big — what now?

Four options when the cable does not withstand
RouteWhat changesWatch out for
Increase the sizek²S² rises with the square of the size. The gain depends on the step: up to 70 mm² one step raises it 2–2.8×; above 95 mm² a step adds 52–78 %If ampacity and voltage drop are already satisfied, this is the most expensive fix
Choose a faster-clearing deviceI²t is directly proportional to time; a current-limiting device can cut the energy several foldDiscrimination may be lost — assess it together with the upstream device
Change the insulationAn insulation that survives a higher temperature raises θf and so k; because k²S² goes with the square of k, the gain in withstand is larger than the gain in kAmpacity rises at the same size too; cable cost goes up
Reduce the fault currentTransformer impedance, run length or a separate board can lower the prospective currentThat is an installation-level decision, not a cable choice

The usual order is: review the protective device first, then the insulation, and the size last. Increasing the size is the most visible fix and often an expensive one.

Frequently Asked Questions

What is a short-circuit thermal withstand calculation?

It checks whether the heat released in a conductor during a short circuit exceeds what the insulation can survive. The condition is I²·t ≤ k²·S²: I is the short-circuit current, t the clearing time, S the nominal cross-sectional area, and k a factor derived from the material and the insulation temperatures. The relation is given for short-circuits lasting up to 5 seconds.

What is the value of k?

There is no single value — it depends on the conductor material, the short-circuit limit temperature of the insulation, and the conductor temperature at the instant the fault begins. This tool does not read k from a ready table; it runs the formula from Annex A of IEC 60364-5-54 with the material constants, rounds to the nearest integer, and tells you when it has rounded upwards. That way it also works for temperatures you enter yourself.

Why do you not publish the k table?

Tables in standards are copyrighted and cannot be republished; translating them is equally out of bounds. The formula and the physical constants, by contrast, are facts. We run the method rather than copying the table. There is a side benefit: a table gives a handful of ready combinations, while the formula works for any pair of temperatures.

Where do I read θi and θf?

From your own cable standard or the cable’s data sheet. θi is the conductor temperature at the instant the fault starts (for a line conductor, the maximum continuous operating temperature); θf is the limit the insulation can survive briefly, given per insulation type in the cable standard. The tool has no ready-made insulation presets: you enter both temperatures, the pre-filled values are only an example, and results computed from them are labelled “(example value)”.

The clearing time is very short — what should I enter?

Below about 0.1 s, or with a current-limiting device, you do not read a time off the curve; you use the manufacturer’s declared let-through I²t (Joule integral). Fuses publish two values — cable protection uses the TOTAL value, while the pre-arcing value is for discrimination studies. The second input mode exists precisely for this.

Doesn’t the adiabatic assumption break down below 0.1 s?

No — the opposite. The shorter the fault, the less heat escapes into the insulation, so the adiabatic assumption holds better. The reason for the threshold is not heat but the current itself: in the first half-cycles the current is asymmetrical (it carries a DC component), and computing with the symmetrical rms value understates the energy. With current-limiting devices there is no readable time left at all.

Why is k different for a protective conductor?

A protective conductor normally carries no load current, so at the instant of the fault it starts at ambient temperature. A conductor starting colder has more thermal headroom, so k comes out higher. But this applies ONLY to a PE outside the cable and not bunched with loaded cores. If the PE is a core of a multicore cable it sits at the same temperature as those cores, and starting it from ambient is dangerously optimistic. Because you enter θi yourself, you make this distinction according to how the cable is built.

Is this check enough for a screened cable?

No. In a screened or armoured cable two separate fault levels are calculated: symmetrical three-phase current for the conductor and line-to-earth current for the screen. Because the screen area is usually much smaller than the line conductor, the screen is often the limiting element. Separate temperature limits and separate k values apply to screens and armour.

Sources

  1. IEC 60364-4-43 — Protection against overcurrent. The thermal withstand check for short-circuit conditions; clause 434.5.2 in the 2008 edition, clause 431.5.4 in the 2023 edition, which is restructured and carries its own mapping table (IEC; the text is copyrighted)
  2. IEC 60364-5-54 — Earthing arrangements and protective conductors. The derivation of k is in normative Annex A (“Method for deriving the factor k in 543.1.2”). The annex is written for the protective-conductor clause; the same derivation holds for line conductors, and the line-conductor k values are published in the k table of IEC 60364-4-43 (IEC; the text is copyrighted)
  3. IEC 60724 — Short-circuit temperature limits of electric cables with rated voltages of 1 kV and 3 kV; one of the primary sources of θf. We do not reproduce its values — read them from your own copy (IEC; the text is copyrighted)
  4. IEC 60949 — Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects. Durations beyond 5 s are the subject of this standard (IEC; the text is copyrighted)
  5. Electrical Installation Guide — Verification of the withstand capabilities of cables under short-circuit conditions, and Sizing of the protective earthing conductor (Schneider Electric; an engineering reference based on IEC 60364)
  6. Cable Short Circuit Ratings (Prysmian; manufacturer technical note — separate fault levels and separate temperature limits for screen and armour)

How we choose sources, verify figures and date our pages is set out in how we source and verify what we publish. Spotted an error? Write to info@aksco.com.tr — verified errors are corrected.

Send your list — your quote is ready within 1 business day.

A list, a photo or an Excel file — whatever is easiest. On standard items we aim to quote the same business day. Custom production, imports or 50+ line lists can take longer; when they do, we tell you the timeline in writing on the day we receive the request.